Data centers’ behind-the-meter natural gas generation could trigger a major methane surge. The episode argues methane (not just CO2) from upstream leaks, midstream gathering, on-site facility leaks, and generator methane slip could make these plants comparable to coal on a holistic basis, and that mitigation is feasible without slowing projects.
Olya Erzak, founder and CEO of Frost Methane; mapped methane sources in on-site gas data centers and identified which levers reduce emissions.
50 GW of new capacity could add ~380 Mt CO2e to US emissions in ~18 months (about half CO2 from combustion, half methane). Methane is 28x CO2 over 100 years and 84x over 20 years; methane also drives major air-quality harm. About 40–50% of the 380 Mt is preventable.
Permian Basin upstream losses ~4% average (best ~0.2%, worst ~2x average); reciprocating engines can slip ~3% methane at full load and up to ~12% at partial load; satellite/flyover data show facility leaks can be significant, especially with many engines spread across large sites. Mitigation examples include buying certified low-leak gas (e.g., MIQ/RMI), requiring fast leak detection/repair, avoiding partial-load operation of reciprocating engines, and adding exhaust methane oxidation/catalysts.
Written by AI. May contain mistakes.
Discussing the prevalence of on-site gas generation for data centers and its implications.
“But an equivalent variable is the methane that actually never gets burned.”
Introduction to the sponsor, GridBeyond, and their offerings for energy management.
Introduction to the sponsor, Antenna Group, and their role in the energy sector.
“For three decades, Antenna has helped ambitious companies stand out, build market leadership, and become category-defining brands.”
Exploring the significance of methane in the context of climate impact and data centers.
“Okay, so I think our listeners probably have some general sense of this, but not nearly as much knowledge as you do about it.”
Exploring the significance of methane in the context of climate impact and data centers.
“interesting analysis on methane emissions that might come from that and then how to mitigate them.”
Detailed analysis of the sources of methane emissions in the data center value chain.
“So, you know, data centers are building this natural gas capacity because it takes too long to interconnect to the grid.”
Discussing the quantification of methane emissions from various stages in the gas supply chain.
“So let's start with the methane slip in the generator because that data set is better.”
Examining the broader climate implications of methane emissions from new data centers.
“Sometimes they're a couple of years out of date, but lots of pretty accurate data there.”
Exploring strategies to mitigate methane emissions in the data center industry.
“Sticking, I guess, with the 380 megaton number, like, can you contextualize that a little bit?”
Learn how data centers can significantly reduce methane emissions impact.
“So that, let's call it 50%, that's 15 % of U.S.”
Discover effective strategies for sourcing low-leak natural gas for data centers.
“but obviously extra pipeline capacity buying that is involved.”
Understand the critical need for rapid leak detection and repair systems.
“We do this over long distance gas transmission as well, right?”
Evaluate the relationship between engine types and methane emissions during combustion.
“And then the last thing is the methane slip, right?”
Explore cost-effective strategies for methane management in data centers.
“Honestly, looking holistically at all of that stuff that you can do, to me, it doesn't seem like it's that hard.”
Uncover the challenges in accurately accounting for methane emissions in data centers.
“Yeah, I mean, I know you've been out talking to the hyperscalers about this and preaching the gospel of methane reduction at data centers.”
Understand the need for standardized protocols in methane reduction efforts.
“But to get there, like what's the interim step in your mind?”
Learn about strategies to deal with unavoidable methane emissions.
“If that is indeed true, then what's the excuse?”
Explore various approaches to address methane emissions in data centers.
“The internal structures and its influence on who can move how fast and on what particular topics has been fascinating.”
Discuss the potential wider benefits of data center improvements on other industries.
“And I think similarly, the catalyst for the slip, on the one hand, we want to do that.”
Wrap up with acknowledgments and information about the production.
“because of all this buying the meter gas.”

Get the gist, explore an idea or ask about something said.
On Catalyst with Shayle Kann, what are the key points of this episode?
Automatic transcript. May contain errors.
0:02Latitude Media, covering the new frontiers of the energy transition. I'm Shayle Kann. I lead early stage investments at Energy Impact Partners. Welcome to Catalyst. So let's take one thing as a given. Behind the meter gas generation for data centers is happening. Interconnection queues run for years, the hyperscalers and frontier labs aren't waiting, and on-site gas is often the fastest route to firm power at scale, at least today. Undeniably, tens of gigawatts are coming in the next couple of years alone, and who knows how much in the long term. So it isn't really a question of whether it's going to get built.
0:37It is a question of how. The emissions story that most people think about for natural gas is about CO2, what happens when you combust the fuel. But an equivalent variable is the methane that actually never gets burned. There are some leaks at the wellhead, some leaks at the generation site, some slips unburned out of the exhaust of the generator, depending on the kind of generator. And if you add those up, at least by the math of my guest today, then an on-site gas plant looks actually kind of like a coal plant from a holistic emissions perspective. In aggregate, we're talking about adding annual emissions just from these behind-the-meter assets that could look like all of global aviation, for example.
1:19But make different choices on sourcing and monitoring, some equipment, some efficiency, and that same plant lands closer to average grid emissions. That's the same fuel and the same megawatts with roughly a 2x swing in emissions. So what does it take and is it realistic? Olya Erzak is the founder and CEO of Frost Methane. She's mapped out where the methane comes from in an on-site gas data center and which levers actually move it. She's coming up next. Thank you. resources in one place. Ready to transform your distributed energy management? Get started at gridbeyond.com. Catalyst is brought to you by Antenna Group, the communications and marketing partner behind the most influential companies in energy, climate, and infrastructure.
2:34For three decades, Antenna has helped ambitious companies stand out, build market leadership, and become category-defining brands. From breakthrough startups to global industry leaders, their team brings the expertise, relationships, and track record to accelerate your momentum. Learn more at antennagroup.com. The power plant for the modern grid isn't a building. It's a network. Energy Hub's DERM's platform connects batteries, EVs, thermostats, and commercial and industrial sites into virtual power plants that over 230 utilities dispatch as reliable grid capacity day in, day out. VPPs deploy in 60 to 100 days at 40 to 60 % less cost than traditional infrastructure, and they perform like conventional generation from day one.
3:18Learn about the flexibility platform for the modern grid at energyhub.com.
3:27Oh yeah, welcome. Thanks, Dale. Okay, so I think our listeners probably have some general sense of this, but not nearly as much knowledge as you do about it. So in brief, why should we care about methane? So everybody knows that it's 28 times more potent than CO2 over the 100-year terms and 84 times more potent over the 20-year terms. What people don't know as much about is that today it accounts for 30 % of the warming that we currently experience. Also, it has pretty major air quality issues. So 850 ,000 premature deaths every year and 860 million crop loss. And this is because methane is a precursor to ground double smog.
4:07Okay. So suffice to say, we care about methane. And it just so happens that we, in the United States mostly, but in other countries as well, to some extent, are on the precipice of building kind of an enormous number of data centers that are powered by on-site natural gas generation of one kind or another. And you've done a bunch of interesting analysis on methane emissions that might come from that and then how to mitigate them. Let's start with like walking through where those emissions would emanate from. There's multiple stages. So kind of walk me through end to end, like where do you get methane emissions from in the full value chain of a behind the meter gas powered data center?
4:49Yeah. So, you know, data centers are building this natural gas capacity because it takes too long to interconnect to the grid. And so first, you need to actually extract that natural gas. So let's say your data center is, hypothetically speaking, located in Texas. You're getting your natural gas from the Permian Basin. And so the two sources of leak there are upstream, right? So the wellhead, and then midstream, the gathering pipes that take it from the wellhead to the processing unit within the basin. So between those two things, 4 % of production is lost. So that is a very significant amount of methane that really could be powering more data centers instead of going into the atmosphere.
5:32The long distance transmission pipelines are mostly fine, right? So that's like has negligible amount of leaks. So that's not something that people should be worrying about. Then you have leaks at the actual facility level, right? And then finally, there's what's called methane slippage. So for anybody that's using reciprocating engines as their generators, as opposed to like turbines or combined cycles or fuel cells, there you have very significant amount of methane that slips from the exhaust unburnt. So those are the four things that people should be paying particular attention to. Okay. And you said 4 % on the extraction leak side, that's presumably average across the Permian.
6:12There's a pretty wide variability, right? Exactly. So you have on the upstream side, the best players are probably leaking like 0.2 % of their production. And of course the worst are, you know, at least double the average. And then on the gathering pipes, that's a little bit more tricky because you don't always control which gathering pipes you're in. So you have to put together both the upstream and the less leaky gathering pipes within that. And there's huge basin-to-basin variation as well, right? Like the Permian Basin, San Joaquin in New Mexico, like the Uinta Basin, those are particularly high leakage.
6:51But if you're, say, getting it from Pennsylvania, from the Marcellus, that's a much, much lower leakage rate for both the wellheads and the gathering pipes. So basin-to-basin variation and player-to-player variation. And we'll come back to that in the how do we mitigate it But just to put numbers to each step of the value chain, so the average of 4 % across the Permian on the extraction side, orient me numerically on like the facility leaks and the potential methane slip at the generator. Yes. So let's start with the methane slip in the generator because that data set is better. For four-stroke lean burn engine, the EPA average when it's running at full capacity is 3 % of the methane coming in, slips out the back unburnt.
7:38If you're running it at partial load, that can be significantly, significantly higher, right? I've seen measurements up to 12 % on that. On the facility leaks, that is probably the weakest from a data set standpoint, because we can't say that these are the same as utility scale facility leaks, right? When you are building a gigawatt power plant for utility, you've got two turbines and like a second stage, right? All in the same building right next to each other. Some of these data centers that are getting built right now are doing 35 reciprocating engines sprawled across a pretty large area in order to generate that same gigawatt.
8:19So that means that the amount of piping and welds and connections that you have goes up quite a bit, and therefore the leaks also go up quite a bit. So there it's, you know, we can make an estimate, and what we're seeing from satellite looks not so great for some players. Right. I mean, can you say more about that, actually? Like, how much fidelity is there in all of this data and why? The data, well, the data for methane slips, like reciprocating engines and turbines and fuel cells and all of that, that is, like, really quite well understood, right? There's newer models. Typically, the manufacturer will have methane slip as just part of their data sheet at full load.
8:59But when you're running at partial load, that's where you typically don't get a characterization from the manufacturer. And that's where it goes up quite a bit, right? You also see it on the efficiency drop. So that is pretty solid. The basin leaks, like those have been done depending on the specific basin, but there's been a lot of flyovers, flyover campaigns with methane sensors that, you know, as well as satellite observations that I think are all pretty good. Sometimes they're a couple of years out of date, but lots of pretty accurate data there. And facilities, because of availability of shortages of equipment, they're being built in pretty bespoke ways.
9:42So you see a lot of variation there. I'm curious on the extraction leak side, is the trend line positive or negative? In other words, are we getting better and better over time at minimizing leakage at the wellhead? Or is it the opposite direction? Great question. I think the best study I've seen on this was from RMI. There was a curious but very logical study that showed that there's some variation based on basically gas prices. So natural gas prices go up. The extractors are willing to spend more money to have people doing more frequent inspections. For example, prices go down. all of a sudden your expensive person doing inspection isn't worth the amount of gas that you, the extra gas that you can sell if you prevent the leak.
10:36And so there's a little bit of that correlation that RMI found. But in general, like I think New Mexico had a big improvement recently. But other than that, I think the gas prices are the big ones, given that the like potential EPA regulations did not end up coming in. Interesting. Okay, so there are all these sources of methane leaks in the value chain. Give us a sense, just like at the high level, using averages, obviously, how much total emissions might this add, given how much new behind-the-meter natural gas capacity is being built or planned? Yeah. So we've done the calculation on assuming that 50 gigawatts of new capacity is coming in.
11:30The latest reports are showing more like 75. And just for context, California has 40 gigawatts of natural gas generation capacity installed. So this is, you know, data centers are no longer a rounding error on our energy usage. Like that world is gone. So assuming that 50 gigawatts, if we're assuming the 7.5 % of methane ends up in the atmosphere, which is what happens if you have some optimistic assumptions on facility leaks and, you know, the upstream, midstream and engine slip. And in that case, we would add basically 380 megatons of CO2E to US emissions in the next 18 months for those 50 gigawatts to come online.
12:17So that's really quite significant. And a lot of that is, or 40 to 50 % of that is preventable if we tackle the methane issue. Right? So that's huge numbers. And this is, of course, not including the CO2 emissions from combustion from the generators themselves. The 380 includes the CO2 emissions. Ah, okay. So how much of it is the CO2? Of that 380, how much is the CO2 from combustion? How much is from the methane upstream? Depending on your assumption, between 50 and 60 % is CO2, and between 40 and 50 % is methane. So there's another way to think about it, which is that, like, if people have been thinking about, okay, how much CO2 are we going to generate because we're building all this new natural gas capacity?
13:03They've got roughly half the equation, actually. The actual warming impact is basically double what they're imagining because there's an equivalent warming effect amount from all the methane upstream of that. Exactly. It's double if you use the 100-year equivalency. If you use the 20-year equivalency, it's much, much worse than that. It ends up being like 724 megatons of CO2e with, at that point, the majority being methane. So there's kind of a big question of like, are we looking at a 100-year time horizon for warming or a 20? If at 20, the methane completely dominates. If 100, then yes, then it's double.
13:45So it might be even worse depending on when you think we will start reducing our emissions. Sticking, I guess, with the 380 megaton number, like, can you contextualize that a little bit? You said it's a lot, but like, how much? Yeah, fair point. So the preventable part, right? So that, let's call it 50%, that's 15 % of U.S. grid emissions is what we can prevent by building these data centers with tackling the methane in mind, right? So that's like the biggest climate in the next 18 months, right? It's not like we're going to stop building the data centers afterwards. So this is like by far the biggest climate lever that I ever had a chance to pull in my career.
14:26I don't know if you had 15 % of electric grid lying on the ground in your career, but I'm like. I'd like to think so, but despite a long career in this space, I don't think I have. Okay, so you said preventable. Let's talk about what it takes to prevent it. And I guess, you know, it makes sense to probably similarly walk through the value chain because there's different things you have to do at each step in the value chain. Starting with the upstream wellhead stuff. Exactly. So in the upstream wellheads, there are two things you can do. A, you can buy it from a basin that has lower leaks, right?
15:01That obviously has a bunch of knock-on effects about where you locate your data center or buying pipeline capacity to pipe the methane from where it's produced to your data center. That is possible. but obviously extra pipeline capacity buying that is involved. So there's one thing you could do. You could buy from the best player within a given basin. So there is a set of certification, let's say MIQ from RMI is one of them, where the best players, according to their certification, leak like 0.2 % of their production. And the additional that those players charge for this like certified low leak natural gas is pretty low.
15:47Now, we can argue whether that's the best standard and how we can improve that standard and so on. But directionally, this is correct, right? Essentially, the fact that there are profitable companies that can leak the methane and not leak the methane, that the inspections roughly end up costing the same or something close to the additional revenue from the gas means that it's very easy for the data center companies. companies to tip everybody into the low-league regime, right? Because we know it's possible, there's existence proofs of the good players that do this. And the good players, you know, the folks that leak less, you know, these aren't like small companies, right?
16:23Like BP is one of the certified ones, for example, in the Permian Basin. So it's large supply that is available at the low-league rates. And the data center people together get to essentially decide who drills the next hole in the Permian Basin, right? And they can make that decision, right? Because this is such significant amounts of natural gas that, especially if they got together and did a coalition for responsible gas buying or something like that, you'd be able to, I think, ship the entire industry, not even just their direct suppliers. I mean, starting with their direct suppliers to that regime.
17:02Midstream, I think very similarly, right? That there are basins that have much lower leakage on that. So I think just the attention to it and the demand and the slight, maybe slightly higher pricing, at least at the beginning, would probably shift that pretty easily. We know how to keep pipes intact. We do this over long distance gas transmission as well, right? It just has different regulations on it. On the onsite, I think like I understand why this is difficult, right? You have the hyperscalers that have a subcontractor that has a subcontractor that has a subcontractor by the time somebody wells on your line, right?
17:39And so this is pretty difficult, and it's not that all of these people are thinking heavily about methane leaks. And so this is something that needs to go down both in the contracts and where there needs to be some certification, and leaks are going to happen. The 35 reciprocating engines to be the equivalent of three across, like, sprawled over like a mile, right? But you do what you can with the quality of construction, but leaks are just going to happen in that kind of a regime. And so having leak detection and repair with really fast response is going to be key both for the climate and for the bottom line because this is methane.
18:21At that point, you've already paid for the methane. The methane that's leaking at the wellhead, those you haven't paid for yet. And of course for safety, right? You have a bad well. That thing is ignitable. You have one smoking colleague and that's not going to be good. This is pressurized gas. So that's, like, I think something that people should be pushing a lot harder on as far as the requirements for specific kinds of detection and response time. And then the last thing is the methane slip, right? Pretty large number there. First, if you have availability of some equivalent efficiency that isn't a reciprocating engine, then you just get less slip.
18:58Like this is just not an issue for fuel cells or turbines or combined cycle if you can get it. Is it an issue for like error derivative turbines or no? I don't think so. But I could double check on those. But I don't think any turbines have this issue. I think they all have much more complete combustion. And then for reciprocating engines, you know, you have this issue. And so, first of all, just don't run them as partial loads. So I know a lot of folks out of, like, the best of intentions are trying to match it to solar production. So shut off half of your reciprocating engines instead of running all of them at partial load is something that people can legitimately do, right?
19:37So the running at partial loads is surprisingly bad for methane slip. And then, you know, just like you have a catalytic converter for your car, you can oxidize methane at the exhaust, right? There's catalysts, there's regenerative thermal oxidizers, although those would need additional energy input at the kind of percentages that you get. And we can dive into the options for either one of those things, but those are essentially your options for that.
20:09For data centers, connecting to the grid quickly means two things. Building distributed energy and having a plan for demand flexibility. GridBeyond helps with both. GridBeyond's DERMS and VPP platform unlocks the potential of distributed assets and dispatches flexibility into the right market at the right time. And this is more than software. GridBeyond supports developers every step of the way. From modeling your highest ROI energy mix to orchestrating the full set of assets around a data center, the track record speaks for itself. GridBeyond manages over 1 ,400 sites and more than 3.7 gigawatts of load across Europe, the UK, and the US.
20:48Learn more at gridbeyond.com or click the link in the show notes. If you work in energy or climate, you already know the company's antenna group has helped build. For three decades, they've been the communications and marketing partner behind the industry's breakout companies, category creators, and market leaders. Today, their team is working across the most consequential areas of the energy economy, from data centers and grid modernization to nuclear, geothermal, storage, critical materials, and next-generation technologies. Antenna helps ambitious companies become the names everyone in the market knows, trusts, and wants to work with.
21:22They build reputation, elevate executives, drive demand, and turn momentum into market leadership. If your company is ready to lead its market, Antenna is ready to help you get there. Visit antennagroup.com. When you harness the power of millions of DERs in a VPP and put artificial intelligence behind the dispatch, the outcomes exceed conventional generation. EnergyHub's DERM's platform has been trained on years of real dispatch data from over 2.6 million DERs, so utilities can plan with confidence. That means consistent load reduction across a four-hour event window, even during the widest, most uncertain peak periods.
22:00Utilities target, shape, and verify capacity down to the meter. Unlock flexible capacity that costs 40-60 % less to deploy than traditional infrastructure in a fraction of the time it takes you to break ground on a peaker plant. Learn more at energyhub.com.
22:22Honestly, looking holistically at all of that stuff that you can do, to me, it doesn't seem like it's that hard. It definitely doesn't seem like it's that expensive relative to anything else that these data centers are spending money on, right? It should be doable. Exactly. I don't think it would add more than a percent to the cost of the data center. And I don't think more importantly, the question is, does it increase your time to market, right? Like time to flops? And the answer is it doesn't, right? And all of these things, like even if you can't do it at that moment, do you leave the hook in to put the catalyst into the exhaust to make it easier as soon as you can afford it or as soon as the technology becomes available or the supply chain constraints are done?
23:04And so those kind of like hook-ins for later, people are just too constrained and are having too much of a race to be thinking about anything kind of like that. And so that's why a third party like us is really useful to be talking to all of these folks to say, look, here's the things that if you do it now, it's going to be a lot cheaper later. Yeah, I mean, I know you've been out talking to the hyperscalers about this and preaching the gospel of methane reduction at data centers. I mean, I guess the first question is like, have they been accounting for this? Historically, have they been, when they, you know, they do like pretty public emissions accounting, are they accounting for all this methane slippage?
23:44Not, mostly not correctly. There are certain things like, like people use a lot of country or even a lot of averages that may be really, really undercounting it in a lot of places. And definitely what we're seeing from satellite, just, just, does not match. So I think there's been a lot of undercounting of that by basically using averages. And to their credit, though, it is unlikely that the person that's doing the accounting has expertise about methane slip. Like even data center builders, not just the hyperscalers, all the way down, right? The number of people that know what methane slip is is tiny, right?
24:27And so I don't fault them for, you know, not having the technical expertise in the different kinds of ways that you can generate electricity from methane. It's just like hyper-specific. And so, but yeah, I do think that there will be a lot of accounting that would need to get adjusted, especially once more of this comes online. You know, if you could wave a magic wand, obviously you would have everybody go do all the things. But to get there, like what's the interim step in your mind? Yeah. Yeah, I mean, I think that some of these things are really cheap and easy and like available now, right?
25:01And some of the stuff is just like some of the things which have like a money, a safety and a climate when are like a no brainer. But really, because there's no methane experts all the way down, it's really useful to just have a central party set the standards, right? Kind of like LEIT sets the building ones, and we set the LEAK standards, right? So I think that is really useful to basically say, well, what should you be asking of your suppliers? And then once you show that you care and that there's an influence to who you choose as your supplier and how much you pay them is related to their quantification and reduction plans for their methane, even if they can't immediately do this because of the kind of race we're in.
25:47I think that gets us a lot of the way in. I mean, you said, you know, even if they can't do this immediately because of the race that we're in, like, there's an extent to which I don't want to give them that pass. Because as you said, I think, look, as a practical matter, you, speed to power is the most important thing right now. And there's so much money behind it and so much momentum behind it. It's, it's, it's, you're like tilting at windmills to propose anything that slows down speed to power. But if, as you're saying, none of these things would actually slow a project down, they might add some fraction of a, percentage of cost to that project.
26:22Let's acknowledge that. But they wouldn't slow it down. If that is indeed true, then what's the excuse? Well, I think that's fair. I think the question is maybe at some larger scale, like at some point, are we going to run out of certified low-leak natural gas producers? Or at some point, do we hit shortages on the catalyst? And the catalyst for the methane That's not a solved problem. There are solutions, but all of these solutions will get a lot better with increased use. So there's definitely a scale issues. But I think in general, I'm with you, but I don't know what influence we necessarily have on those.
27:01I don't know if you're willing to name names, but is anybody out in front on this? Any of the hyperscalers? Historically, if you look at who's been out in front on early renewable PPAs or 24-7 clean power, usually it was Google followed by Microsoft, followed by Meta and AWS behind them. Is it kind of a similar dynamic here or is nobody out in front at this point? I think I would be breaking some NDAs if I were to say that, but there are definitely, there is a big difference in the players. But yeah, sorry. Yes, but there's definitely, it's been very interesting to see the internal organizations of the various companies, right?
27:50Like who has how many sustainability people, whether having more sustainability people means that you can move faster on this or not. Not like all of these things have been. I think I understand a little bit more what management consultants do now after this experience. The internal structures and its influence on who can move how fast and on what particular topics has been fascinating. I guess to close out, I mean, you know, you said 380 megatons, plus or minus, of which half is avoidable through this set of measures. That leaves half, which is still 190 megatons. still a lot. What do you do about the other half?
28:31What a great question. I mean, really, there's only two things that you can do, right? Like you can capture the CO2 on site. I did the math on that. That would take about 15 % of their energy. And we know that energy that isn't going to the flops is the one thing currently people aren't willing to give up. So pay to take out or prevent an equivalent amount of emission somewhere else, right? So this is offsetting. And this is something that could be potentially done in the interim of can you offset what you can't reduce? You know, of course, there is can you combine it with more renewables? I think a lot of people are trying that.
29:17You know, can you combine it with the grid under certain circumstances? You know, that obviously still runs into the interconnection queue issues, which is why They filled the gas in the first place. But I think using the gas less and less and less and then offsetting and then maybe eventually capturing when somehow the energy becomes available and you're still using those, that might be another issue. The other thing that I would say is planning a little bit for the future in case these things continue to be around. So, for example, none of them are planning to add a second stage later. And as far as getting 50 % more energy from exactly the same amount of gas, like that reduces your emissions dramatically while also helping a lot on the energy availability and the money.
30:07Those kinds of things, like people are now building structures which do not allow you to add a second stage later when those second stages become available. So I think that's like one of the biggest mistakes we're seeing people make. And I think the one other thing, like I'll say, is I think if there was a massive shift for the data center people to care about this problem, I think the benefits will go beyond the data centers themselves. If you can shift the entire oil and gas industry and eventually, as a result of that shift, make more cheaper methane leak detection and response systems available and more deployed at scale, that could be good for any usage of natural gas, not just the data centers.
30:53And I think similarly, the catalyst for the slip, on the one hand, we want to do that. Data centers are the ones that have the margins to potentially pay that extra percent. But over time, you can imagine that that could be applicable to any reciprocating engines, just like we need to have a catalytic converter on our car. this could now become a standard thing that you just buy and bolt on as opposed to have to like design a little bit more bespoke for each case. So I think that it could move, like it could develop technologies that would move other industries into a better place because now they're available without having to spend so much of your, so much extra.
31:36Not to say that it's a lot in data center terms, but it is a lot for a lot of other industries that wouldn't be able to foot some of the scale-up costs. Well, yeah, this was really informative. And I also very much appreciate that you were doing this work. Like, I think I had an intuitive sense, but I had not seen prior to seeing what the work that you've been doing, anything quantitative on just how much methane we are soon to emit in all likelihood, barring some change because of all this buying the meter gas. So thank you for that. Thanks, Shail. This was super fun. Olya Urzak is the founder and CEO of Frost Methane.
32:13This show is a production of Latitude Media. You can head over to latitudemedia.com for links to today's topics. This episode is produced by Max Savage-Levinson, mixing and theme song by Sean Marquand, and Bailey edits the video version of the show. Stephen Lacey is our executive editor. All of our episodes are on YouTube. Subscribe to Latitude Media for episodes of this show and Open Circuit. You can also find the audio version of the show anywhere you get your podcasts. I'm Shail Khan, and this is Catalyst.
It’s no secret that hyperscalers’ behind-the-meter gas bonanza has generated enormous CO2 emissions. But the AI boom is responsible for another, less-publicized emissions issue: upstream and onsite methane leaks that could derail decarbonization efforts.
In this episode, Shayle Kann speaks with Olya Irzak, founder and CEO of Frost Methane Labs. Olya unpacks the full lifecycle of methane emissions in gas-powered data centers, and considers why the actual warming impact of behind-the-meter gas may be double current estimates. Olya says practical, relatively low-cost strategies could cut those emissions in half. Shayle and Olya also discuss:
- The big-picture data: Why tens of gigawatts of new behind-the-meter gas capacity could generate 380 megatons of CO2 and methane emissions over the next 18 months.
- How methane can leak across the value chain, from wellheads and gathering pipelines to facility leaks and engine slippage
- How methane's extreme short-term warming potency means off-grid gas emissions could dwarf coal’s impacts over the next 20 years
- Why running gas generators at partial loads increases leaks
- Why low-leak gas procurement, leak detection and repair, and catalyst additions add less than 1% to total data center build costs without causing operational delays
- How big tech's current emissions reporting relies on averages that overlook actual leaks
- Catalyst: The unexplored frontier of methane removal
- Catalyst: Why are we still flaring gas?
- Catalyst: Serving data center load with carbon capture
- Catalyst: Can the fossil gas supply handle the AI boom?
- Open Circuit: The off-grid data center fantasy
- Latitude Media: The problem with the US gas bonanza for data centers
- Latitude Media: Senate Democrats probe gas-powered AI data centers
Credits: Hosted by Shayle Kann. Produced and edited by Max Savage Levenson. Original music and engineering by Sean Marquand. Stephen Lacey is our executive editor.
Catalyst is brought to you by GridBeyond. GridBeyond is the world’s leading technology platform for managing distributed and flexible energy resources. Learn more by visiting GridBeyond.com.
Catalyst is brought to you by Antenna Group, the strategic communications and marketing partner behind the biggest names in energy, climate, and infrastructure. For three decades, Antenna has helped breakout companies amplify their stories, build reputation, differentiate from the competition, define new categories and accelerate growth. Learn more at antennagroup.com.
Catalyst is brought to you by EnergyHub. Peak season puts every grid to the test — and the utilities that pass are the ones that built flexible capacity before they needed it. EnergyHub works with more than 230 utilities to coordinate over 2.6 million DERs and more than 3.6 gigawatts of dispatchable flexibility through a single platform designed to perform when it counts most. See what that looks like at EnergyHub.com.